Is it possible to shut down an individual compressor for load shedding purposes?

(CP1, CP1A,CP1B, CP2. CP2A, CP2B, 111111)

Parameters CP1 to CP2B (up to 6 steps) can be used to shut down an individual compressor requiring shut down for load shedding purposes. Each compressor up six is identified by a 1 in the number string 111111. The individual compressor will not start up if its identifier has been switched to 0 unless contact m11 3-4 is closed. If the remote contact m11 3-4 is open all other compressors identified by 1 will operate. This parameter is useful when starting compressors during the service checks.