Is it possible to shut down an individual compressor without affecting the other compressors in the circuit of setting off alarms?

(CP1 power, CP1A power, CP1B power, CP2 power, CP2A power, CP2B power)

Parameters CP1 power to CP2B power (up to 6 steps) can be used to shut down an individual compressor requiring service or for reasons. The compressors % of load number must be changed to zero. The GR3 will not look for the compressor which has a 0 % service value set into this function. All general and safety controls directly related to this specific compressor only will be overlooked. All other compressors showing a unit % will run and operate as needed.  Upon completion of the service for the compressor requiring shut down return the power parameter % to its normal value. The compressor will start up in the next cycle.