What is the minimum volume of stored water content required to operate an ANK series unit?

The recommended volume of stored water is 10 liters per kilowatt ( or 9.3 gal/ton) in order for the ANK series unit to work properly. The minimum value is 4 liters per kilowatt.

Model

Normal Capacity

 Factory Tank Min Clg. Content
ANK030

2.51 T

26 Gal

23 Gal

ANK045

3.35 T

36 Gal

31 Gal

ANK050

4.02 T

36 Gal

37 Gal