Where do I find the service information to setup the Aermec NRL GR3 controller to manage my project?

The GR03/GR3 controller user manual can be used to set up all stand-alone and BMS installations which will operate with standard environmental conditions. Do not attempt to adjust the control parameters without having read and understood the manual. The NRL unit arrives with a basic operating program ready to start up …

Is it possible to shut down an individual compressor without affecting the other compressors in the circuit of setting off alarms?

(CP1 power, CP1A power, CP1B power, CP2 power, CP2A power, CP2B power) Parameters CP1 power to CP2B power (up to 6 steps) can be used to shut down an individual compressor requiring service or for reasons. The compressors % of load number must be changed to zero. The GR3 will …

What happened if a compressor fails to start or shut down on its compressor protection module or other circuit safety device?

(MP1, MP1A, MP1B, MP2, MP2A, MP2B, RMV1, RMV2) If any of the compressor protection (wired in series) devices trip the safety circuits M9.1 to M9.2 or M12.1 to M12.2 is opened shutting down the NRL circuit completely. A solution is to disconnect the defective compressor or control electrically. Install a …

What happened if an outdoor fan motor fails to start or shut down on its overload?

(MT(V)1, MT(V)1A, MT(V)1B, MT(V)2, MT(V)2A, MT(V)2B, RMV1, RMV2) If any of the fan protection (wired in series) devices trip the safety circuits M9.1 to M9.2 or M12.1 to M12.2 is opened a solution is to disconnect the defective motor or control electrically. Install a jumper on the overload or relay control contacts. …

Do I need to remove all of the refrigerant from the NRL unit when changing the pressure controls of transducers?

Chillers, free cooling units, heat pumps The low pressure and high pressure transducers can be removed from the system without removing the charge from the system as they are fitted with a schraeder check fitting. Units that are fitted with a low pressure switch from the factory are also equipped with a …

Do I need to remove all of the refrigerant from the NRL when changing compressor or high pressure switch?

Chillers and free cooling units only, not for heat pumps Close the liquid line valve. Pump down the compressor section. Close the hot gas line. Reclaim the refrigerant trapped between the evaporator and hot gas line by accessing the schraeder valve in the hot gas line. Make the repairs. Pressure test. …

Do I need to remove all of the refrigerant from the NRL unit when changing the oil in the compressor(s)?

Chillers and free cooling units only, not for heat pumps depending on the model of the NRL the liquid line and discharge lines are equipped with isolating valves. The liquid line valve can be closed, the compressor section can be pumped down to one or two pounds, the hot gas line …

Do I need to remove all of the refrigerant from the NRL unit when changing the compressor(s) after a mechanical unit?

Depending on the size of the NRL the liquid line and discharge lines are equipped with isolating valves. The liquid line valve can be closed, the compressor section can be pumped down to one or two pounds, the hot gas line valve can be closed. The remaining refrigerant pressure can be vented. …

Do I need to remove all of the refrigerant from the NRL unit when changing the compressor(s) after a burnout?

Chillers, free cooling units, heat pumps Depending on the model of the NRL the liquid line and discharge lines are equipped with isolating valves. The liquid line the refrigerant charge must be completely replaced along with the liquid line filters in the case of a burnout. All of the oil in the …

What happens if a high pressure event occurs locking out the compressors on a NRL 0600 to 3600 chillers, free cooling, heat pumps, 2 to 4 circuits – up to 3 compressors per circuit?

The AP (HP) transducer is factory set to 39 bar (565 PSIG). The manual AP (HP) manual reset switch is set for 42 bar (609 PSIG). The AP (HP) relief valve is set to release refrigerant at 45 bar (652 PSIG). It is possible that the unit will totally shut …

What happens if a high pressure event occurs locking out the compressors on a NRL 0280-0750, 0800-1800, 2000-3600?

Chillers, free cooling, heat pumps. 2 circuits up to 3 compressors per unit. The press f. Parameter can also be used on units with as few as 2 compressors. The transducer will shut off one compressor.  Wait 5 minutes (time out). Then the GR3 will turn the compressor back on. If the …

Do I need to remove all of the refrigerant from the NRL unit when changing the oil in the compressor(s)?

Chillers and free cooling units only, not for heat pumps Depending on the size of the NRL the liquid line and discharge lines are equipped with isolating valves. The liquid line valve can be closed, the compressor section can be pumped down to one or two pounds, the hot gas line …

What happens if a replacement Moducontrol is a different version number than the original control?

The updated replacement Moducontrol replaces all previous versions of the control. The new module must be addressed via the dipswitches and internal electronic switch according to the new revised manual. New Module Revision Number. Use New Manual. Any new features that are built into the new Moducontrol will automatically be part of …