How do you reset the Moducontrol back to the factory settings?

Change menu functions by pressing the screwdriver symbol. Enter password 125 by using the arrow keys. Confirm password by pressing the screwdriver symbol again. The Moducontrol display will indicate # 0 or 1. Using the arrow up key scroll to position # 0. Using the screwdriver symbolenter the parameter. Existing parameter should read # 1. Change parameter …

How do you start or stop the unit as a Stand-A-Lone unit?

Change menu functions by pressing the screwdriver symbol. Enter password 30 by using the arrow keys. Confirm password by pressing thescrewdriver symbol again. The Moducontrol display will indicate # 0. Using the arrow up key scroll to position # 0. Using the screwdriver symbol enter the parameter. Existing parameter should read # 0. If not; change parameter by …

How do you change the unit from heating to cooling as a Stand- A-Lone unit?

Change menu functions by pressing the screwdriver symbol. Enter password 30 by using the arrow keys. Confirm password by pressing the screwdriver symbol again. The Moducontrol display will indicate # 0. Using the arrow up key scroll to position # 0. Using the screwdriver key enter the parameter. Existing parameter should read # 0. If not; change parameter by …

How do you adjust cooling temperature?

Change menu functions by pressing the screwdriver symbol. Enter password 000 by using the arrow keys. Confirm password by pressing the screwdriver symbol again. The Moducontrol display will indicate # 1 Stf. Using the screwdriver key enter the parameter. Existing parameter should read # set temperature. Change parameter by using the up or down arrow and toggle …

How do you adjust heating temperature?

Change menu functions by pressing the screwdriver symbol. Enter password 000 by using the arrow keys. Confirm password by pressing the screwdriver symbol again. The Moducontrol display will indicate # 3 StC. Using the screwdriver key enter the parameter. Existing parameter should read # set temperature. Change parameter by using the up or down arrow and toggle …

How do I turn the compensation temperature (outdoor / indoor reset) On or Off?

The ANK Moducontrol has the ability to adjust the outlet water temperature being supplied to the building according to the changing outdoor temperature in both cooling and heating modes. The changes in water temperature are the inverse of the falling or rising outdoor temperature. Cooling and heating temperature compensation is available if …

How do you set up domestic hot water temperature (maximum to 130 deg. F. or 50 deg. C.)?

Change menu functions by pressing the screwdriver symbol. Enter password 000 by using the arrow keys. Confirm password by pressing the screwdriver key again. The Moducontrol display will indicate # 1. Using the arrow up key scroll to position # E SAS. Using the screwdriver key the parameter. Existing parameter should read # set DHW temperature. Change …

Unit is running in heating. Moducontrol display indicates a cooling (snowflake) caller. Outdoor Coil is cooling. Indoor Coil is heating.

Change menu functions by pressing the screwdriver symbol. Enter password 333 by using the arrow keys. Confirm password by pressing the screwdriver key again. The Moducontrol display will indicate # 1. Using the arrow up key scroll to position # 3.  Using the screwdriver key enter the parameter. Existing parameter should read # 0. Change parameter by …

Unit is running in cooling. Moducontrol display indicates a heating (sun) caller. Outdoor Coil is heating. Indoor Coil is cooling.

Change menu functions by pressing the screwdriver symbol. Enter password 333 by using the arrow keys. Confirm password by pressing the screwdriver symbol again. The Moducontrol display will indicate # 1. Using the arrow up key scroll to position # 3.  Using the screwdriver key enter the parameter. Existing parameter should read # 1. Change parameter by using …

How do you set up domestic hot water differential (20 deg. F. or 10 deg. C.)?

Change menu functions by pressing the screwdriver symbol. Enter password 000 by using the arrow keys. Confirm password by pressing the screwdriver key again. The Moducontrol display will indicate # 1. Using the arrow up key scroll to position # F bAS. Using the screwdriver key enter the parameter. Existing parameter should read # set differential. Change parameter …

How do you set up time delay for DHW diverting valve? (Use timing to open from valve mfg. + allowance)

Change menu functions by pressing the screwdriver symbol. Enter password xxx  by using the arrow keys. Confirm password by pressing the screwdriver key again The Moducontrol display will indicate # 1. Using the arrow up key scroll to position # 8 r in. Using the screwdriver key enter the parameter. Existing parameter should read # 1. Change …

How do you limit the compressor operation? (During periods of time when boiler integration is taking place)

This error can occur when boiler is following ANK indoor outdoor reset parameters at ODT below 0 deg. C. Change menu functions by pressing the screwdriver symbol. Enter password 030 by using the arrow keys. Confirm password by pressing the screwdriver key again. The Moducontrol display will indicate # 1. Using the arrow up key scroll to position # H Ati. …

No heating or cooling. Error code 104 is displayed on Moducontrol. Flow Switch Error.

If the flow switch or differential switch opens the Moducontrol will alarm and stop the unit. On startup the Moducontrol will allow up to forty (40) seconds for the pump to establish flow before temporarily alarming. The unit will try to start until the number of interventions exceeds the maximum shut downs …