No cooling or heating. Error code 124 is displayed on Moducontrol. No charge.

The compressor is running with extremely low current and may not have enough refrigerant. Check refrigerant charge, superheat, and subcooling. Check soft starter, capacitors, compressor windings, contactor, and wiring. Check voltage and amperage. Check condition of the condensing coil. Check for items limiting heat rejection.

No cooling or heating. Error code 129 is displayed on Moducontrol. Compressor stalling.

The compressor is running with extremely low current and may not have enough refrigerant. Check refrigerant charge, superheat, and subcooling. Check soft starter, capacitors, compressor windings, contactor, and wiring. Check voltage and amperage. Check condition of the condensing coil. Check for items limiting heat rejection.

No heating or cooling. Error code 156 is displayed on Moducontrol. Cycle reversal due to high pressure.

The unit has gone into defrost without waiting for the correct time between defrosts to be completed. The capacity control threshold was terminated due to high discharge temperatures (130 deg. C.). This pre-alarm does not cause the system to stop and there is no limit to the number of interventions.