The outdoor fans do not start or run properly with DCPX / Penn P66AA-1C speed controller.

The Moducontrol supplies 0 to 10 volts dc and 230 volts ac to the Penn P66AA-1C. The Speed Controller ramps up to 90 % of the normal fan speed for 7 seconds and then begins to modulate to the required speed. The Speed Controller provides power to the fan motor for as long as the cooling caller …

What causes the outdoor fan to modulate in the domestic hot water mode?

Moducontrol dipswitch # 7 to on. Set parameter A to 1. Set parameter E to 1. Set parameter F is set between 60 and 300 seconds depending on the time required to open the three way valve. The TWS switch automatically overrides the space heating controls to provide hot water. Please Note installer level index 0 parameter iu must be set to 2. Domestic hot water heating is …

What controls are recommended for DCPX control of chillers and heat pumps?

The SAGInoMIYA RGE pressure actuated speed controller can be used on ANK series units designated as chillers only. The Johnson Controls P66AA-1C speed controller is approved for chillers and heat pumps. It is necessary for Domestic Hot Water Production (DHW). Required for Cooling Operation below 20 Deg. C. Required for mild weather space heating and DHW production.

How do you set up the ANK series units to produce Domestic Hot Water (DHW)?

The production of hot water can be handled in two different ways. Integrated and free standing. The most common method is to integrate the process completely into the ANK control system. (1) Integrated Operation The DHW thermostat sensor is to be installed into the storage tank. The control wires from the DHW thermostat send a signal to a three …