101

Compressor thermomagnetic switch. Fan thermomagnetic switch. Pump thermomagnetic switch This warning appears if the contact of the thermomagnetic switch protecting the MTC compressor is opened.

102

Fan thermomagnetic switch. This warning appears if the contact of the thermomagnetic switch protecting the MTV fan is opened. This code is displayed only if the card is used as a replacement for cards with SW up to version 3.6.

103

High pressure switch. This warning does NOT indicate the status of the high pressure switch itself, but of the compressor contactor. The high pressure switch acts directly on the compressor contactor. If the card con-trols the switch-on of the compressor, and the contactor is not activated after 3 seconds, this …

104

Flow switch. Water differential pressure switch. This warning appears with the opening of the contact relating to the flow switch or to the differential pressure switch. This alarm is not detected in the first 40 seconds from when the pump is switched on. The machine goes into lockout when the …

105

Low pressure switch. This warning appears with the opening of the contact of the low pressure switch (intake on the compressor) BP.

108

Water freeze. This warning appears when the anti-freeze temperature threshold (installer menu, parameter (6) default: 3°C) of the outlet water is reached. The pre-alarm condition is removed when the outlet water temperature exceeds the setpoint calculated by the card on the basis of an internal algorithm; the anti-freeze alarm is …

110

High force gas temperature. This warning appears when the force gas temperature (SGP probe) exceeds the threshold set in the parameter. The pre-alarm condition is removed with the factory-set temperature (default 125°C).

111

No compressor delivery pressure transducer. This warning appears when the compressor delivery transducer is not detected and the machine is set in heat pump mode, or the presence of the DCP is set.

112

High pressure. This warning appears when the transducer detects a delivery pressure greater than the set threshold (default: 40 bar). The pre-alarm condition is removed with the factory-set pressure (default: 38 bar).

113

No defrosting probe. This warning appears when the defrosting probe is absent and the machine is set in heat pump mode.

114

No compressor suction pressure transducer. This warning appears when the compressor suction transducer is absent and the machine is set in heat pump mode.

115

Low pressure. This warning appears when the compressor delivery transducer detects a suction pressure lower than the factory-set threshold in cool mode (default: 4 bar), or in heat mode (default : 2 bar). The prealarm condition is removed when the suction pressure exceeds the envisaged intervention threshold (default equal to …

116

Low output. Whenever the machine is powered, the control checks the behavior of the compressor once only, via the output control procedure. This control can be deactivated by means of the dip-switch.

117

Pump thermomagnetic switch. This warning appears if the contact of the thermomagnetic switch protecting the pump is opened. MTP. This code is displayed only if the card is used as a replacement for cards with SW up to version 3.6.

118

High pressure capacity control. This warning appears whenever there is a capacity control due to the set threshold being reached. The machine goes into lockout when the maximum number of capacity controls allowed (default 5) is exceeded. With the inverter machine, it also indicates a capacity control due to a …

119

Low pressure capacity control. This warning appears whenever there is a low pressure capacity control. The machine goes into lockout when the maximum number of capacity controls allowed (default 5) is exceeded.

120

Discharge temperature capacity control. This warning appears whenever there is a discharge temperature capacity control. The machine goes into lockout when the maximum number of capacity controls allowed (default 5) is exceeded.

121

Bemf error (chiller inverter) – error in the detection of the back emf. This error is given by the inverter control card and is linked to compressor pickup current problems.